This current transformer, standard for busbar, has a line rated current of 400 A and a secondary current rating of 5 A. This current transformer do have a 55 mm x 85 mm opening. Compatible with a single output for bar: 50 mm x 80 mm. Burden and accuracy class as follows: class 0.5 maximum power: 1 VA.
Specifications:
- Range: PowerLogic
- Product Name: CT
- Product or Component Type: Current transformer
- Secondary Current: 5 A
- Accuracy Class: Class 0.5 at 1 VA
- Rated Current ([In]): 400 A
- Complementary:
- Current Transformer Type: Standard for busbar, Split core
- Current Transformer Ratio: 400/5
- [Ith] Conventional Free Air Thermal Current: 400 A
- Maximum Safety Factor: 5
- Permissible Current: 24000 A during 1 s
- [Ue] Rated Operational Voltage: < 720 V 50 Hz
- [Ui] Rated Insulation Voltage: 3 kV
- Mounting Mode:
- By screws
- Mounting support:
- DIN rail
- Fastened onto a surface with screws
- Dimensions:
- Width:
- Outside: 125 mm
- Inner: 55 mm
- Height:
- Outside: 158.15 mm
- Inner: 85 mm
- Depth: 58 mm
- Electrical Insulation Class: Class E
- Opening of Bars: 50 x 80
- Environment:
- Standards:
- VDE 0414
- DIN 42600-2
- DIN EN 61869-1
- DIN EN 61869-2
- Ambient Air Temperature for Operation: -5…40 °C
- Ambient Air Temperature for Storage: -25…70 °C