- Product Family : I/O Systems: Active - Standalone
- Product Sub Family : LioN-Xlight
- Item Description : 0980 LSL 3211-121-0006-004
- Device Type : IO-Link Master
- Protocol : EtherCAT
- I/O Function : 8 IOL (Class A)
- Bus Connection : M12, 4-poles, D-coded
- Power Connection (System Supply) : M12 Power, 5-poles, L-coded
- I/O Connection : M12, 5-poles, A-coded
- I/O Type : IO-Link Master
General Data
- Housing Material : Metal, zinc die-cast
- Housing Plating : Nickel, matt
- Housing Color : Grey Metallic
- Protection Degree / IP Rating : IP65, IP67, IP69K
- Potted : Yes
- Dimensions (W x H x D) : 60 mm x 31 mm x 200 mm
- Weight : 500 g
- Ambient Temperature (Operation) : -20 °C to 60 °C
- Ambient Temperature (Storage/Transport) : -20 °C to 60 °C
- Permissible Humidity (Operation) : 5 % ... 95 % (For UL applications max. 80 %)
- Permissible Humidity (Storage/Transport) : 5 % ... 95 % (For UL applications max. 80 %)
- Air Pressure (Operation) : 80 kPa … 106 kPa (up to 2000 m above sea level)
- Air Pressure (Storage/Transport) : 80 kPa … 106 kPa (up to 2000 m above sea level)
- Flammability Class : UL 94 (IEC 61010)
- Protection Class : III, IEC 61140, EN 61140, VDE 0140-1
- Pollution Degree : 3 acc. to EN 60664-1, VDE 0110-1
- Vibration Resistance : 15 g / 5 -500 Hz
- Shock Resistance : 50 g / 11ms
- Contact Base Material : M12, D-coded, CuSn, Gold-plated | M12 Power, L-coded, CuNi, Gold-plated
- Contact Bearer Material : PA / TPU
- O-Ring Material : FKM
- Mounting : 2 hole screw mounting. Use standard M4 x 25 / 30 screws with toothed lock washer (as per DIN 125) and self-locking nuts.
- Fastening Torque (Fixing Screw) : M4: 1 Nm
- Fastening Torque (Ground Connection (FE)) : M4: 1 Nm
- Fastening Torque (Bus Connection) : M12: 0.5 Nm
- Fastening Torque (Power Connection) : M12: 0.5 Nm
- Fastening Torque (I/O Connection) : M12: 0.5 Nm
- Accessories to Order Separately : Ethernet cable, mounting adapter, sensor/actuator cable, power cable
EtherCAT
- Protocol : EtherCAT
- Connection : M12 4-poles, D-coded
- Number of Connections : 2
- Specification : ETG.1000 V1.2
- Transmission Rate : Fast Ethernet (10/100 Mbit/s), Full Duplex
- Transmission Method : 100 BASE-TX, with auto negotiation and auto crossing
- Cycle Time / Update Rate : min. 250 µs
- Addressing : Auto-increment addressing, fixed position addressing
- Mailbox Protocols : CANopen over EtherCAT (CoE), File access over EtherCAT (FoE), Ethernet over EtherCAT (EoE)
- Supported Network Protocols (Other) : Over EoE: HTTP, Ping, TCP/IP, Modbus TCP, REST API
- Cyclic data read/write : Diagnosis data, Event data
Power Supply
- Connection Module Supply Voltage : M12 Power, 5-poles, L-coded
- Number of Connections : 2
- Module Supply Voltage (Nominal) : 24 V DC (SELV/PELV)
- Module Supply Voltage (Range) : 20V DC to 30 V DC
- Reverse Polarity Protection : Yes
- Status Indicator (System Supply) : LED green
- Diagnostic Indicator : LED red
- Connection Sensor Supply Voltage : M12 Power, 5-poles, L-coded
- Sensor Supply Voltage (Nominal) : 24 V DC (SELV/PELV)
- Sensor Supply Voltage (Range) : 20V DC to 30 V DC
- Reverse Polarity Protection : Yes
- Status Indicator (Sensor Supply) : LED green
- Diagnostic Indicator : LED red
IO-Link Master Channels
- Number of IO-Link Master Channels : max. 8, configurable
- Connection : M12, 5-poles, A-coded
- IO-Link Class A Ports : 8x, X1 to X8
- IO-Link Specification : V1.1.3
- Parameter Storage : Supported
- Supported COM Modes : 4.8 kBaud (COM 1), 38.4 kBaud (COM 2), 230.4 kBaud (COM 3)
- Cycle Time / Update Rate : min. 1 ms for all channels at 32 Byte IN / OUT
- Nominal Current 1L+ (Pin 1) : 2A
- Nominal Voltage : 24 V DC via US (system power supply)
- Nominal Current C/Q (Pin 4) : 500mA
- Perm. Conductor Length to Device : ≤ 20 m
- Status Indicator (IOL) : LED green per channel
- Diagnostic Indicator : LED red per port
Digital Input Channels
- Number of Digital Input Channels : up to 16
- Connection : M12, 5-poles, A-coded
- Number of Ports : 8x, X1 to X8
- Channel Type : Type 1 acc. to IEC 61131-2
- Input Wiring : 2-, 3-, 4-wire
- Nominal Voltage : 24 V DC via US (module power supply)
- Nominal Current : typ. 5 mA
- Sensor Current Supply : max. 4A per port via Pin1L+
- Sensor Type : PNP
- Input Voltage Range "0" signal : -3 V DC …+5 V DC
- Input Voltage Range "1" signal : 15 V DC ... 30 V DC
- Input Filter Time : configurable
- Protective Circuit : Electronically: Overload protection, short-circuit protection
- Status Indicator (Inputs) : LED white or yellow per channel
- Diagnostic Indicator : LED red per port
Digital Output Channels
- Number of Digital Output Channels : up to 8
- Connection : M12, 5-poles, A-coded
- Number of Ports : 8x, X1 to X8
- Channel Type : p-switching
- Output Wiring : 2-, 3-wire
- Nominal Voltage : 24 V DC via US
- Output Current per Channel : max. 500mA
- Galvanically Isolated : No
- Protective Circuit : Electronically: Overload protection, short-circuit protection
- Overload Behavior : Auto off and on switching / Manual restart
- Status Indicator (Outputs) : LED white or yellow per channel
- Diagnostic Indicator : LED red per port
Electrical Isolation
- US (System Supply Voltage) / FE : 500 V DC
- US / UL (Actuator Supply Voltage) : 500 V DC
- UL / FE : 500 V DC
- Uaux / FE : 500 V DC
- Bus connection / FE : 2000 V DC
EMC Conformance
- EMC Directive : 2014/30/EU
- EN 61000-4-2 Electrostatic Discharge (ESD) : Criterion B; 4 kV contact discharge, 8 kV air discharge
- EN 61000-4-3 Electromagnetic Field : Criterion A; Field intensity: 10 V/m
- EN 61000-4-4 Fast Transients (Burst) : Criterion B, 2 kV
- EN 61000-4-5 Surge Voltage : Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); For I/O ports with cables ≤ 30m
- EN 61000-4-6 Conducted immunity : Criterion A; Test voltage 10 V
- EN 55032 Radio Interference Properties : Class A
Safety & Environmental Compliance
- CE : Yes
- RoHS Compliant : Yes
- China RoHS-Compliant : Yes
Approvals
- UL : cULus Listed, UL 61010-1
- CSA : Yes, via UL
- ETG : Yes
- IO-Link : Yes
Notes
- Protection Degree / IP Rating Note : IP Rating test performed by Belden with Belden Connectors only
- System Power Supply Connection Note : Do not connect / disconnect under voltage!