Current Consumption (typical): 180 mA (at 24 V DC)
Reverse Polarity Protection: Yes
Current Carrying Capacity (Connectors): Up to 16 A per connector
I/O-Links (Channels & Configuration):
IO-Link Master Channels: Max. 8, configurable
Class A Ports: 4x (X1 to X4)
Class B Ports: 4x (X5 to X8)
IO-Link Specification: V1.1.2
Supported COM Modes: 4.8 kBaud, 38.4 kBaud, 230.4 kBaud
Cycle Time / Update Rate: Min. 8 ms for all channels at 32 Byte IN / OUT
Digital Inputs & Outputs:
Digital Input Channels:
Number of Channels: Max. 12, configurable
Channel Type: Type 1 (IEC 61131-2)
Input Voltage: 0V to 30 V DC (PNP)
Protective Circuit: Overload and short-circuit protection
Input Status Indicator: LED (White or Yellow per channel)
Digital Output Channels:
Number of Channels: Max. 8, configurable
Output Type: p-switching, 2-wire
Output Current per Channel: Max. 0.5 A (Pin 4)
Output Current per Module: Max. 9 A
Protective Circuit: Overload and short-circuit protection
Output Status Indicator: LED (White or Yellow per channel)
Electrical Isolation & EMC Conformance:
Electrical Isolation: 500 V DC (System Supply) / FE, 2000 V DC (Bus connection)
EMC Conformance: EN 61000-4-2 (ESD), EN 61000-4-3 (Electromagnetic Field), EN 61000-4-4 (Fast Transients), EN 61000-4-5 (Surge Voltage), EN 55022 (Radio Interference)