- Product Family: I/O Systems: Active - Standalone
- Product Sub Family: LioN-S
- Item Description: 0930 CSL 650
Device Type
Protocol
I/O Function
Bus Connection
Power Connection (System Supply)
I/O Connection
I/O Type
- Digital In-/Output (Universal)
Product Life Cycle
- Housing Material: PBT + ASA
General Data
- Protection Degree / IP Rating: IP67
- Housing Color: Black
- Potted: No
- Dimensions (W x H x D): 30 mm x 40 mm x 205 mm
- Weight: 200 g
- Ambient Temperature (Operation): -10 °C to 60 °C
- Vibration Resistance: 15 g / 5 -500 Hz
- Shock Resistance: 50 g / 11ms
- Mounting: 2 hole screw mounting. Use standard M4 x 25 / 30 / 40 (lateral) screws with toothed lock washer (as per DIN 125) and self-locking nuts.
- Fastening Torque (Fixing Screw): M4: 1 Nm
- Fastening Torque (Ground Connection (FE)): M4: 1 Nm
- Fastening Torque (Bus Connection): M12: 0.5 Nm
- Fastening Torque (Power Connection): M12: 0.5 Nm
- Fastening Torque (I/O Connection): M8: 0.3 Nm
- Included in Delivery:
- Attachable Labels: 10x
- Sealing Caps: 2x M8
CANopen
- Connection: M12, 5-poles, A-coded
- Number of Connections: 2
- Device Profile: CiA 401
- Communication Profile: CiA 301
- Transmission Rate: 10 kbps … 1 Mbps
- Transmission Rate Adjustment: Automatic
- Addressing via Rotary Address Switches: 1 … 127 dec
- Emergency Messages (EMCY): Supported
- Modular EDS File: Not supported
Power Supply
- Connection Module Supply Voltage: M12, 5-poles, A-coded
- Number of Connections: 2
- Current Carrying Capacity of Connector: max. 4 A
- Module Supply Voltage (Nominal): 24 V DC (SELV/PELV)
- Module Supply Voltage (Range): 19 V DC to 30 V DC
- Current Consumption (typ.): 65 mA (at 24 V DC)
- Reverse Polarity Protection: Yes
- Status Indicator (System Supply): LED green
- Diagnostic Indicator: No
- Connection Sensor Supply Voltage: M12, 5-poles, A-coded
- Number of Connections: 1
- Current Carrying Capacity of Connector: max. 4 A
- Sensor Supply Voltage (Nominal): 24 V DC (SELV/PELV)
- Sensor Supply Voltage (Range): 19 V DC to 30 V DC
- Reverse Polarity Protection: Yes
- Status Indicator (Sensor Supply): LED green
- Diagnostic Indicator: No
- Connection Actuator Supply Voltage: M12, 5-poles, A-coded
- Number of Connections: 1
- Current Carrying Capacity of Connector: max. 4 A
- Actuator Supply Voltage (Nominal): 24 V DC (SELV/PELV)
- Actuator Supply Voltage (Range): 19 V DC to 30 V DC
- Reverse Polarity Protection: Yes
- Status Indicator (Actuator Supply): LED green
- Diagnostic Indicator: No
Digital Input Channels
- Number of Digital Input Channels: max. 8, universal
- Connection: M8, 3-poles, A-coded
- Number of Ports: 8x, 1 to 8
- Channel Type: Type 3 acc. to IEC 61131-2
- Sensor Current Supply: max. 100 mA per port (at 30°C)
- Input Wiring: 2-, 3-wire
- Nominal Voltage: 24 V DC via US (module power supply)
- Nominal Current: typ. 5 mA
- Sensor Type: PNP
- Input Voltage Range "0" signal: -3 V DC …+5 V DC
- Input Voltage Range "1" signal: 11 V DC … 30 V DC
- Input Filter Time: 1 ms, fixed
- Protective Circuit: Electronically: Overload protection, short-circuit protection
- Status Indicator (Inputs): LED yellow per channel
- Diagnostic Indicator: LED red per port
Digital Output Channels
- Number of Digital Output Channels: max. 8, universal
- Connection: M8, 3-poles, B-coded
- Number of Ports: 8x, X1 to X8
- Output Current per Channel: max. 0.5 A
- Channel Type: p-switching
- Output Wiring: 2-, 3-wire
- Nominal Voltage: 24 V DC via UL (actuator power supply)
- Output Current per Module: max. 4 A
- Galvanically Isolated: No
- Protective Circuit: Electronically: Overload protection, short-circuit protection
- Overload Behavior: Auto off and on switching / Manual restart
- Status Indicator (Outputs): LED yellow per channel
- Diagnostic Indicator: LED red per channel
Electrical Isolation
- US (System Supply Voltage) / FE: 500 V DC
- US / UL (Actuator Supply Voltage): 500 V DC
- UL / FE: 500 V DC
- Bus connection / FE: 500 V DC
EMC Conformance
- EMC Directive: 2014/30/EU
- EN 61000-4-2 Electrostatic Discharge (ESD): Criterion B; 4 kV contact discharge, 8 kV air discharge
- EN 61000-4-3 Electromagnetic Field: Criterion A; Field intensity: 10 V/m
- EN 61000-4-4 Fast Transients (Burst): Criterion B, 2 kV
- EN 61000-4-5 Surge Voltage: Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); For I/O ports with cables ≤ 30m
- EN 61000-4-6 Conducted immunity: Criterion A; Test voltage 10 V
- EN 55022 Radio Interference Properties: Class A
Safety & Environmental Compliance
- CE: Yes
- RoHS Compliant: Yes
Approvals
- UL: cULus Listed, UL 508
- UL-File: E230848
Notes
- Protection Degree / IP Rating Note: Only if mounted and locked in combination with Hirschmann / Lumberg Automation connector.
- System Power Supply Connection Note: Do not connect / disconnect under voltage!