Shopping List
购物清单
CNY - ¥
Image
/
/
/
/
施耐德电气 TM251MESC 逻辑控制器、Modicon M251、以太网
施耐德电气 TM251MESC 逻辑控制器、Modicon M251、以太网
Image
Image
Specifications
infotip-icon
View other Programmable Logic Controllers dimensions or variations
Please select at least one specification below.
Product Or Component Type
Logic controller
Range Of Product
Modicon M251
Standards
ANSI/ISA 12-12-01 CSA C22.2 No 142 CSA C22.2 No 213 IEC 61131-2:2007 Marine specification (LR, ABS, DNV, GL) UL 508
Ip Degree Of Protection
IP20 with protective cover in place
Relative Humidity
10…95 %, without condensation (in operation) 10…95 %, without condensation (in storage)
Ambient Air Temperature For Operation
-10…35 °C (vertical installation) -10…55 °C (horizontal installation)
Ambient Air Temperature For Storage
-25…70 °C
Operating Altitude
0...2000 m
Product Certifications
cULus CE UKCA DNV-GL ABS LR
[Us] Rated Supply Voltage
24 V DC
Local Signalling
1 LED (green) for PWR 1 LED (green) for RUN 1 LED (red) for module error (ERR) 1 LED (red) for I/O error (I/O) 1 LED (green) for SD card access (SD) 1 LED (red) for BAT 1 LED (green) for Ethernet port activity 1 LED (green) for SL 1 LED (red) for bus fault on TM4 (TM4) 1 LED (green) for CANopen run 1 LED (green) for CANopen error
This spec is not available in the specification table.
Mounting Support
Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 plate or panel with fixing kit
This spec is not available in the specification table.
Pollution Degree
2
This spec is not available in the specification table.
Power Consumption In W
32.6…40.4 W (with max number of I/O expansion module)
This spec is not available in the specification table.
Realtime Clock
With
This spec is not available in the specification table.
Insulation
Non-insulated between supply and internal logic Between supply and ground at 500 V AC
This spec is not available in the specification table.
Communication Port Protocol
USB port: USB - SoMachine-Network Non isolated serial link: Modbus master/slave - RTU/ASCII or SoMachine-Network
This spec is not available in the specification table.
Marking
CE
This spec is not available in the specification table.
Maximum Number Of Connections
8 Modbus server 8 Modbus client 16 Ethernet/IP target 4 FTP server 10 web server 8 SoMachine protocol
This spec is not available in the specification table.
Shock Resistance
15 gn for 11 ms
This spec is not available in the specification table.
Vibration Resistance
3.5 mm at 5…8.4 Hz on symmetrical rail 3 gn at 8.4…150 Hz on symmetrical rail 3.5 mm at 5…8.4 Hz on panel mounting 3 gn at 8.4…150 Hz on panel mounting
This spec is not available in the specification table.
Resistance To Electrostatic Discharge
8 kV in air conforming to IEC 61000-4-2 4 kV on contact conforming to IEC 61000-4-2
This spec is not available in the specification table.
Resistance To Fast Transients
2 kV (power lines) conforming to IEC 61000-4-4 1 kV (Ethernet line) conforming to IEC 61000-4-4 1 kV (serial link) conforming to IEC 61000-4-4
This spec is not available in the specification table.
Immunity To Microbreaks
10 ms
This spec is not available in the specification table.
Supply Voltage Limits
20.4…28.8 V
This spec is not available in the specification table.
Communication Service
DHCP client Downloading Ethernet/IP slave device IEC VAR ACCESS Modbus TCP client Modbus TCP server Modbus TCP slave device Monitoring NGVL Programming Updating firmware SMS notifications FTP client/server SNMP client/server SQL client Send and receive email from the controller based on TCP/UDP library Web server (WebVisu & XWeb system) OPC UA server DNS client
This spec is not available in the specification table.
Backup Time
2 years at 25 °C
This spec is not available in the specification table.
Clock Drift
<= 60 s/month at 25 °C
This spec is not available in the specification table.
Integrated Connection Type
USB port with mini B USB 2.0 connector Non isolated serial link serial with RJ45 connector and RS232/RS485 interface Dual-port Ethernet with RJ45 connector CANopen J1939 with SUB-D 9 connector
This spec is not available in the specification table.
Surge Withstand
1 kV shielded cable common mode conforming to IEC 61000-4-5 1 kV power lines common mode conforming to IEC 61000-4-5 0.5 kV power lines differential mode conforming to IEC 61000-4-5
This spec is not available in the specification table.
Resistance To Electromagnetic Fields
10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3 1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3
This spec is not available in the specification table.
Electromagnetic Emission
Conducted emissions - test level: 120...69 dBµV/m QP ( power lines) at 10…150 kHz conforming to IEC 55011 Conducted emissions - test level: 63 dBμV/m QP ( power lines) at 1.5…30 MHz conforming to IEC 55011 Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to IEC 55011 Conducted emissions - test level: 79...63 dBμV/m QP ( power lines) at 150…1500 kHz conforming to IEC 55011 Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to IEC 55011
This spec is not available in the specification table.
Inrush Current
50 A
This spec is not available in the specification table.
Electrical Connection
removable screw terminal blockpower supply (pitch 5.08 mm)
This spec is not available in the specification table.
Port Ethernet
Ethernet marking 10BASE-T/100BASE-TX - 2 copper cable
This spec is not available in the specification table.
Resistance To Conducted Disturbances
10 V 0.15...80 MHz conforming to IEC 61000-4-6 3 V 0.1...80 MHz conforming to Marine specification (LR, ABS, DNV, GL) 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
This spec is not available in the specification table.
Storage Altitude
0…3000 m
This spec is not available in the specification table.
Maximum Number Of I/O Expansion Module
7 (local I/O-Architecture) 14 (remote I/O-Architecture)
This spec is not available in the specification table.
Memory Capacity
64 MB for system memory RAM
This spec is not available in the specification table.
Data Backed Up
128 MB built-in flash memory for backup of user programs
This spec is not available in the specification table.
Data Storage Equipment
<= 16 GB SD card (optional)
This spec is not available in the specification table.
Battery Type
BR2032 lithium non-rechargeable, battery life: 4 year(s)
This spec is not available in the specification table.
Execution Time For 1 Kinstruction
0.3 ms for event and periodic task 0.7 ms for other instruction
This spec is not available in the specification table.
Supply
(serial)serial link supply: 5 V, <200 mA
This spec is not available in the specification table.
Transmission Rate
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m for RS485 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m for RS232 480 Mbit/s for bus length of 3 m for USB
This spec is not available in the specification table.
Application Structure
3 cyclic master tasks + 1 freewheeling task 8 event tasks 4 cyclic master tasks 8 external event tasks
This spec is not available in the specification table.
Web Services
Web server
This spec is not available in the specification table.
Number Of Server Device(S)
63 CANopen:
This spec is not available in the specification table.
Canopen Feature Profile
DR 303-1 DS 301 V4.02
This spec is not available in the specification table.
产品描述
¥ 7980.86
数量:
EA
Shop by Specification Table
You can find items with similar specifications from the table below.
Programmable Logic Controllers
45 Items
programmable-logic-controllers-img
Product Or Component Type
Discrete I/O extension module, Modular smart relay, Compact smart relay, Compact discovery packs, Programmable controllers
Range Of Product
Modicon M251, Easy Modicon M200, Modicon M221, Modicon M171/M172, SpaceLogic KNX
Standards
IEC 61131-2 UL 508 CAN/CSA C22.2 No. 213 IACS E10 ANSI/ISA 12-12-01, CAN/CSA-E60730-1<br />CSA E60730-2-9<br />EN 60068-2-27<br />EN 60068-2-6 Fc<br />EN 60730-1<br />EN 60730-2-9<br />UL 60730-1<br />UL 60730-2-9<br />IEC 61000-4-2<br />IEC 61000-4-3<br />IEC 61000-4-4<br />IEC 61000-4-5<br />IEC 61000-4-6<br />IEC 61000-4-11<br />UL94 (material V0), IEC 61000-4-5<br />IEC 61000-4-3<br />IEC 61000-4-2<br />EN 60068-2-27<br />EN 60730-1<br />EN 60068-2-6 Fc<br />UL 60730-1<br />UL 60730-2-9<br />IEC 61000-4-4<br />CAN/CSA-E60730-1<br />IEC 61000-4-11<br />IEC 61000-4-6<br />CSA E60730-2-9<br />EN 60730-2-9<br />UL94 (material V0), CSA, UL, CSA Certified, UL Listed
Ambient Air Temperature For Operation
-10…35 °C (vertical installation) -10…55 °C (horizontal installation), -10…50 °C (vertical installation) -10…55 °C (horizontal installation), -20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2 -20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2, -20…65 °C conforming to UL 60730-1<br />-20…60 °C horizontal conforming to UL 60730-1, -20…60 °C conforming to UL 60730-1<br />-20…65 °C with derating conforming to UL 60730-1
Product Certifications
GL C-Tick CSA UL GOST, GOST CSA UL C-Tick GL, DNV-GL EAC ABS cULus LR RCM CE UKCA cULus HazLoc, EAC<br />CE<br />cURus<br />CSA<br />RCM, CSA<br />EAC<br />RCM<br />CE<br />cURus
[Us] Rated Supply Voltage
24 V, 100...240 V AC, 24 V +/- 10 % AC<br />20...38 V DC, 24 V dc, 4.75 → 5.25 V
-
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
来自 SCHNEIDER ELECTRIC 的 Programmable Logic Controllers
寻找和比较同类产品
更多来自 Programmable Logic Controllers
用更广泛的选择扩大您的搜索范围
最近浏览过的 产品
比较和参考以前查看的项目
Image