Shopping List
购物清单
CNY - ¥
Image
/
/
/
/
施耐德电气 A9L20501 1P + N - iPRD20r 模块化浪涌保护器
施耐德电气 A9L20501 1P + N - iPRD20r 模块化浪涌保护器
Image
Image
Specifications
infotip-icon
View other Surge Protection Devices dimensions or variations
Please select at least one specification below.
Colour
White (RAL 9003)
Device Short Name
iPRD20r
Product Or Component Type
Surge arrester with pluggable cartridge
Poles Description
1P + N
Standards
EN 61643-11:2012 IEC 61643-11:2011
Tightening Torque
2.5 N.m
[Ue] Rated Operational Voltage
230/400 V AC (+/- 10 %) at 50/60 Hz
Earthing System
TN-S TT
Surge Arrester Technology
MOV + GDT
[Ipe] Ground Residual Current
0.003 mA 0.6 mA
Product Name
Acti9 iPRD
This spec is not available in the specification table.
Device Application
Distribution
This spec is not available in the specification table.
Mounting Mode
Clip-on (DIN rail)
This spec is not available in the specification table.
Range Of Product
Acti9
This spec is not available in the specification table.
Quality Labels
KEMA-KEUR NF
This spec is not available in the specification table.
Connections - Terminals
Tunnel type terminal (downside) 2.5…35 mm² Tunnel type terminal (upside) 2.5…35 mm²
This spec is not available in the specification table.
9 Mm Pitches
4
This spec is not available in the specification table.
Relative Humidity
5…95 %
This spec is not available in the specification table.
Ambient Air Temperature For Operation
-25…60 °C
This spec is not available in the specification table.
Ambient Air Temperature For Storage
-40…85 °C
This spec is not available in the specification table.
Operating Altitude
2000 m
This spec is not available in the specification table.
Product Certifications
CE
This spec is not available in the specification table.
Ik Degree Of Protection
IK03 conforming to IEC 62262
This spec is not available in the specification table.
Signal Contacts Composition
1 SD (1 C/O)
This spec is not available in the specification table.
Remote Signalling
With
This spec is not available in the specification table.
Surge Arrester Type
Electrical distribution network
This spec is not available in the specification table.
Surge Arrester Class Type
Type 2
This spec is not available in the specification table.
[In] Nominal Discharge Current
Common mode: 5 kA (L/PE) Common mode: 5 kA (N/PE) Differential mode: 5 kA (L/N)
This spec is not available in the specification table.
[Imax] Maximum Discharge Current
Common mode: 20 kA L/PE Common mode: 20 kA N/PE Differential mode: 20 kA L/N
This spec is not available in the specification table.
[Uc] Maximum Continuous Operating Voltage
Common mode: 260 V N/PE Common mode: 350 V L/PE Differential mode: 350 V L/N
This spec is not available in the specification table.
Maximum [Up] Voltage Protection Level
Differential mode <1.1 kV type 2 L/N Common mode <1.4 kV type 2 N/PE
This spec is not available in the specification table.
[Ut] Temporary Overvoltage
337 V L/N 5 s withstand 1200 V N/PE 200 ms safe failure mode 442 V L/PE 5 s withstand 1453 V L/PE 200 ms safe failure mode
This spec is not available in the specification table.
Disconnector Device Type
Associated circuit breaker IC60N 20 A curve C - Icu 10 kA Associated circuit breaker iC60H 20 A curve C - Icu 15 kA Associated circuit breaker iC60L 20 A curve C - Icu 25 kA Associated circuit breaker NG125H 20 A curve C - Icu 36 kA Associated circuit breaker NG125L 20 A curve C - Icu 50 kA Associated fuse gG 40 A - Icu 15 kA Associated fuse gG 80 A - Icu 50 kA
This spec is not available in the specification table.
Signalling Circuit Voltage
0.25 A/250 V AC 50/60 Hz
This spec is not available in the specification table.
产品描述


¥ 5656.82
数量:
EA
Img
最小6 EA单位起订量
Img
1 EA 一捆
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
来自 SCHNEIDER ELECTRIC 的 Surge Protection Devices
寻找和比较同类产品
更多来自 Surge Protection Devices
用更广泛的选择扩大您的搜索范围
最近浏览过的 产品
比较和参考以前查看的项目
Image
最佳