65 kA Icu at 230/240 V AC 50/60 Hz
50 kA Icu at 400/415 V AC 50/60 Hz
50 kA Icu at 440 V AC 50/60 Hz
12 kA Icu at 500 V AC 50/60 Hz
6 kA Icu at 690 V AC 50/60 Hz
This spec is not available in the specification table.
Width
55 mm
This spec is not available in the specification table.
Device Short Name
GV3P
This spec is not available in the specification table.
Product Name
TeSys GV3
TeSys Deca
This spec is not available in the specification table.
Depth
136 mm
This spec is not available in the specification table.
Device Application
Motor protection
This spec is not available in the specification table.
Network Type
AC
This spec is not available in the specification table.
Network Frequency
50/60 Hz
This spec is not available in the specification table.
Utilisation Category
AC-3 conforming to IEC 60947-4-1
This spec is not available in the specification table.
Suitability for Isolation
Yes conforming to IEC 60947-1
This spec is not available in the specification table.
Standards
EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
This spec is not available in the specification table.
Height
132 mm
This spec is not available in the specification table.
Mechanical Durability
50000 cycles
This spec is not available in the specification table.
Electrical Durability
20000 cycles for AC-3 at 415 V In
This spec is not available in the specification table.
Tightening Torque
5 N.m - on screw clamp terminal
This spec is not available in the specification table.
Fixing Mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws)
This spec is not available in the specification table.
Motor Power kW
37 kW at 400/415 V AC 50/60 Hz
45 kW at 500 V AC 50/60 Hz
55 kW at 690 V AC 50/60 Hz
This spec is not available in the specification table.
[Ith] conventional free air thermal current
73 A conforming to IEC 60947-4-1
This spec is not available in the specification table.
Power dissipation per pole
8 W
This spec is not available in the specification table.
Product certifications
CCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
ABS
DNV-GL
UKCA
This spec is not available in the specification table.
Climatic withstand
conforming to IACS E10
This spec is not available in the specification table.
Fire resistance
960 °C conforming to IEC 60695-2-11
This spec is not available in the specification table.
Mechanical robustness
Shocks: 5 Gn for 11 ms contactor open
Shocks: 30 Gn for 11 ms contactor closed
Vibrations: 4 Gn, 5...300 Hz
This spec is not available in the specification table.
[Ics] rated service short-circuit breaking capacity
100 % at 230/240 V AC 50/60 Hz
60 % at 400/415 V AC 50/60 Hz
60 % at 440 V AC 50/60 Hz
50 % at 500 V AC 50/60 Hz
50 % at 690 V AC 50/60 Hz
This spec is not available in the specification table.
Thermal protection adjustment range
62…73 A conforming to IEC 60947-4-1
This spec is not available in the specification table.
Magnetic tripping current
1120 A
This spec is not available in the specification table.
Phase failure sensitivity
Yes conforming to IEC 60947-4-1
This spec is not available in the specification table.
Rated duty
Continuous conforming to IEC 60947-4-1
This spec is not available in the specification table.
IK Degree of Protection
IK09 enclosure
This spec is not available in the specification table.