Shopping List
Shopping List
SGD - S$
Image
Abb OT16F3 Switch-Disconnector
Brand:
ABB
Model:
OT16F3
Image
Image
Technical Data Sheets
Product Description

ABB OT16F3 Switch-Disconnector

  • Extended Product Type: OT16F3
  • Product ID: 1SCA104811R1001
  • EAN: 6417019389554
  • Catalog Description: OT16F3 Switch-Disconnector
  • Long Description: 3-pole, front operated, base mounted, DIN-rail mountable switch-disconnector / non-fusible disconnect switch with protected clamp terminals
  • Handle and Shaft: Not included

Technical Specifications

  • Cable Cross-Section: Cu 0.75–10 mm²
  • Color: Grey
  • Conventional Free-Air Thermal Current (Ith): 25 A at 40°C
  • Conventional Thermal Current (Ithe): 25 A, fully enclosed
  • Distance Between Phases: Standard
  • Handle Type: Knob
  • Mechanical Durability: 20,000 operations
  • Mounting Type: Base mounting
  • Number of Poles: 3P
  • Operating Mode: Front
  • Position of Line Terminals: Top In – Bottom Out / Bottom In – Top Out
  • Power Loss: 0.3 W per pole at rated operating conditions
  • Terminal Type: Screw terminals
  • Tightening Torque: 0.8 N·m according to IEC 60947-1
  • Wire Stripping Length: 9–10 mm for main circuit
  • Recommended Screwdriver: Pozidriv 2 for main circuit
  • Special Functions: None
  • Switch Operating Mechanism: Mechanism on top of the switch
  • Standards: IEC 60947-3 / UL 508 / CSA C22.2 No. 14

Connecting Capacity – Main Circuit

  • Flexible with Ferrule: 1 × Cu 0.75–4 mm²
  • Solid: 1 × Cu 0.75–6 mm²
  • Flexible: 1 × Cu 0.75–10 mm²
  • Stranded: 1 × Cu 0.75–10 mm²

Rated Electrical Characteristics

  • Rated Insulation Voltage (Ui): 750 V according to IEC/EN 60664-1
  • Rated Impulse Withstand Voltage (Uimp): 8 kV
  • Rated Operational Voltage: 750 V, main circuit
  • Rated Operational Current AC-21A (Ie):
    • 16 A at 380–415 V
    • 16 A at 500 V
    • 16 A at 690 V
  • Rated Operational Current AC-22A (Ie):
    • 16 A at 380–415 V
    • 16 A at 500 V
    • 16 A at 690 V
  • Rated Operational Current AC-23A (Ie):
    • 16 A at 380–415 V
    • 16 A at 500 V
    • 10 A at 690 V
  • Rated Operational Power AC-23A (Pe):
    • 3 kW at 220–240 V
    • 7.5 kW at 400–415 V
    • 7.5 kW at 500 V
    • 7.5 kW at 690 V
  • Rated Conditional Short-Circuit Current (Inc):
    • 50 kA with 40 A fuse at ≤415 V
    • 50 kA with 25 A fuse at 690 V
  • Rated Short-Circuit Making Capacity (Icm): 0.71 kA at 690 V
  • Rated Short-Time Withstand Current (Icw): 0.5 kA for 1 second

UL/CSA Specifications

  • Maximum Operating Voltage: 600 V
  • Ampere Rating: 20 A
  • Tightening Torque: 7 in-lb
  • Horsepower Rating:
    • 1 Hp at 110–120 V AC, single phase
    • 2 Hp at 240 V AC, single phase
    • 5 Hp at 440–480 V AC, single phase
    • 7.5 Hp at 550–600 V AC, single phase
    • 5 Hp at 220–240 V AC, three phase
    • 10 Hp at 440–480 V AC, three phase
    • 10 Hp at 550–600 V AC, three phase
Switch Disconnectors from ABB
Source & compare similar products
More from Switch Disconnectors
Expand your search with a wider selection
Recently Viewed Products
Compare & Refer to previously viewed items
Image