Shopping List
Daftar Belanja
IDR - Rp
Image
/
/
/
/
Penggerak Kecepatan Variabel Schneider Electric ATV340D37N4E, Mesin Altivar ATV340, 37kW, Tugas Berat, 400V, 3 Fase, Ethernet
Penggerak Kecepatan Variabel Schneider Electric ATV340D37N4E, Mesin Altivar ATV340, 37kW, Tugas Berat, 400V, 3 Fase, Ethernet
Image
Image
Image
Specifications
infotip-icon
View other Inverter Drives dimensions or variations
Please select at least one specification below.
Range of Product
Altivar Machine ATV340
Mounting Mode
Wall mount
Standard
IEC 61800-3 IEC 61800-5-1 IEC 60721-3 IEC 61508 IEC 13849-1 UL 618000-5-1 UL 508C IEC 61000-3-12
IP Degree of Protection
IP20
Ambient Air Temperature for Operation
-15…50 °C without derating (vertical position) 50…60 °C with derating factor (vertical position)
Ambient Air Temperature for Storage
-40…70 °C
Operating Altitude
<= 4800 m with current derating above 1000m
[Us] Rated Supply Voltage
380...480 V - 15...10 %
Supply Frequency
50...60 Hz +/- 5 %
Switching Frequency
2...16 kHz adjustable 4...16 kHz with derating factor
Noise Level
63.5 dB
Transmission Rate
4.8 kbit/s 9.6 kbit/s 19.2 kbit/s 38.4 kbit/s
Power Dissipation in W
Natural convection: 90 W at 380 V, switching frequency 4 kHz (heavy duty) Forced convection: 796 W at 380 V, switching frequency 4 kHz (heavy duty) Natural convection: 105 W at 380 V, switching frequency 4 kHz (normal duty) Forced convection: 943 W at 380 V, switching frequency 4 kHz (normal duty)
Continuous Output Current
88 A at 4 kHz for normal duty 74.5 A at 4 kHz for heavy duty
Line Current
79.8 A at 380 V with internal line choke (normal duty) 69.1 A at 480 V with internal line choke (normal duty) 67.1 A at 380 V with internal line choke (heavy duty) 59 A at 480 V with internal line choke (heavy duty) 67.1 A 59.0 A
Apparent Power
57.4 kVA at 480 V (normal duty) 49.1 kVA at 480 V (heavy duty)
Maximum Transient Current
105.6 A during 60 s (normal duty) 105.6 A during 2 s (normal duty) 111.8 A during 60 s (heavy duty) 111.8 A during 2 s (heavy duty)
Maximum Input Current
79.8 A
Maximum Output Voltage
480 V
Nominal Output Current
74.5 A
Width
213.0 mm
This spec is not available in the specification table.
Product or Component Type
Variable speed drive
This spec is not available in the specification table.
Depth
262.0 mm
This spec is not available in the specification table.
Height
660.0 mm
This spec is not available in the specification table.
Overvoltage Category
Class III
This spec is not available in the specification table.
Pollution Degree
2
This spec is not available in the specification table.
Marking
CE
This spec is not available in the specification table.
Analog Input Type
AI1 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits AI1 software-configurable temperature probe or water level sensor AI1 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits AI2 software-configurable voltage: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
This spec is not available in the specification table.
Electromagnetic Compatibility
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
This spec is not available in the specification table.
Motor Power kW
45 kW for normal duty 37 kW for heavy duty
This spec is not available in the specification table.
Motor Power hp
60 hp for normal duty 50 hp for heavy duty
This spec is not available in the specification table.
Minimum Switching Current
Relay output R1B: 5 mA at 24 V DC Relay output R2C: 5 mA at 24 V DC
This spec is not available in the specification table.
Certifications
UL CSA TÜV EAC CTick
This spec is not available in the specification table.
Operating Position
Vertical +/- 10 degree
This spec is not available in the specification table.
Product Specific Application
Machine
This spec is not available in the specification table.
Protection Type
Thermal protection: motor Safe torque off: motor Motor phase loss: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent: drive Output overcurrent between motor phase and earth: drive Output overcurrent between motor phases: drive Short-circuit between motor phase and earth: drive Short-circuit between motor phases: drive Motor phase loss: drive DC Bus overvoltage: drive Line supply overvoltage: drive Line supply undervoltage: drive Input supply loss: drive Exceeding limit speed: drive Break on the control circuit: drive
This spec is not available in the specification table.
Connector Type
3 RJ45
This spec is not available in the specification table.
Output Voltage
<= power supply voltage
This spec is not available in the specification table.
Discrete Input Number
8
This spec is not available in the specification table.
Analogue Input Number
3
This spec is not available in the specification table.
Assembly Style
With heat sink
This spec is not available in the specification table.
Maximum Switching Current
Relay output R1C on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1C on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC Relay output R2C on resistive load, cos phi = 1: 5 A at 250 V AC Relay output R2C on resistive load, cos phi = 1: 5 A at 30 V DC Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
This spec is not available in the specification table.
Electrical Connection
Control: screw terminal 0.75...1.5 mm²/AWG 18...AWG 16 Line side: screw terminal 35...50 mm²/AWG 2...AWG 1 DC bus: screw terminal 35...50 mm²/AWG 3...AWG 1 Motor: screw terminal 50 mm²/AWG 1
This spec is not available in the specification table.
Network Number of Phases
3 phases
This spec is not available in the specification table.
Discrete Output Number
1.0
This spec is not available in the specification table.
Regulation Loop
Adjustable PID regulator
This spec is not available in the specification table.
Maximum Output Frequency
0.599 kHz
This spec is not available in the specification table.
Physical Interface
2-wire RS 485
This spec is not available in the specification table.
Analogue Output Number
2
This spec is not available in the specification table.
Analogue Output Type
Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits Software-configurable current AQ1, AQ2: 0...20 mA impedance 500 Ohm, resolution 10 bits
This spec is not available in the specification table.
EMC Filter
Class C3 EMC filter integrated
This spec is not available in the specification table.
Method of Access
Slave Modbus RTU Slave Modbus TCP
This spec is not available in the specification table.
Type of Cooling
Forced convection
This spec is not available in the specification table.
Communication Port Protocol
Modbus TCP Modbus serial EtherNet/IP
This spec is not available in the specification table.
Variant
Standard version
This spec is not available in the specification table.
Degree of Protection
UL type 1
This spec is not available in the specification table.
Asynchronous Motor Control Profile
Optimized torque mode Variable torque standard Constant torque standard
This spec is not available in the specification table.
Synchronous Motor Control Profile
Reluctance motor Permanent magnet motor
This spec is not available in the specification table.
Nominal Switching Frequency
4 kHz
This spec is not available in the specification table.
Prospective Line Isc
50 kA
This spec is not available in the specification table.
Discrete Input Type
PTI safe torque off: 0…30 kHz, 24 V DC (30 V) DI1...DI5 programmable as pulse input, 24 V DC (30 V), impedance: 3.5 kOhm programmable
This spec is not available in the specification table.
Discrete Output Type
Programmable output DQ1, DQ2 30 V DC 100 mA
This spec is not available in the specification table.
Relay Output Number
3
This spec is not available in the specification table.
Relay Output Type
Relay outputs R1A Relay outputs R1C electrical durability 100000 cycles Relay outputs R2A Relay outputs R2C electrical durability 100000 cycles
This spec is not available in the specification table.
Transmission Frame
RTU
This spec is not available in the specification table.
Number of Addresses
1…247
This spec is not available in the specification table.
Data Format
8 bits, configurable odd, even or no parity
This spec is not available in the specification table.
Type of Polarization
No impedance
This spec is not available in the specification table.
4 Quadrant Operation Possible
True
This spec is not available in the specification table.
Acceleration and Deceleration Ramps
Linear adjustable separately from 0.01...9999 s S, U or customized
This spec is not available in the specification table.
Motor Slip Compensation
Adjustable Can be suppressed Automatic whatever the load Not available in permanent magnet motor law
This spec is not available in the specification table.
Braking to Standstill
By DC injection
This spec is not available in the specification table.
Brake Chopper Integrated
True
This spec is not available in the specification table.
Base Load Current at High Overload
74.5 A
This spec is not available in the specification table.
Base Load Current at Low Overload
88.0 A
This spec is not available in the specification table.
With Safety Function Safely Limited Speed (SLS)
True
This spec is not available in the specification table.
With Safety Function Safe Brake Management (SBC/SBT)
True
This spec is not available in the specification table.
With Safety Function Safe Operating Stop (SOS)
False
This spec is not available in the specification table.
With Safety function Safe Position (SP)
False
This spec is not available in the specification table.
With Safety Function Safe Programmable Logic
False
This spec is not available in the specification table.
With Safety Function Safe Speed Monitor (SSM)
False
This spec is not available in the specification table.
With Safety Function Safe Stop 1 (SS1)
True
This spec is not available in the specification table.
With sft fct Safe Stop 2 (SS2)
False
This spec is not available in the specification table.
With Safety Function Safe Torque Off (STO)
True
This spec is not available in the specification table.
With Safety Function Safely Limited Position (SLP)
False
This spec is not available in the specification table.
With Safety Function Safe Direction (SDI)
False
This spec is not available in the specification table.
Isolation
Between power and control terminals
This spec is not available in the specification table.
Maximum THDI
<48 % full load conforming to IEC 61000-3-12 <48 % 80 % load conforming to IEC 61000-3-12
This spec is not available in the specification table.
Environmental Class (During Operation)
Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3
This spec is not available in the specification table.
Maximum Acceleration Under Shock Impact (During Operation)
150 m/s² at 11 ms
This spec is not available in the specification table.
Maximum Acceleration Under Vibrational Stress (During Operation)
10 m/s² at 13...200 Hz
This spec is not available in the specification table.
Maximum Deflection Under Vibratory Load (During Operation)
1.5 mm at 2...13 Hz
This spec is not available in the specification table.
Permitted Relative Humidity (During Operation)
Class 3K5 according to EN 60721-3
This spec is not available in the specification table.
Volume of Cooling Air
240.0 m3/h
This spec is not available in the specification table.
Ambient Air Transport Temperature
-40…70 °C
This spec is not available in the specification table.
Option Card
Communication module, PROFINET Communication module, DeviceNet Communication module, CANopen Communication module, EtherCAT
This spec is not available in the specification table.
Number of Preset Speeds
16 preset speeds
This spec is not available in the specification table.
Deskripsi Produk

Rp 94.404.837
Kuantitas:
EA
This item is sold by
Image
Schneider Electric
0
Shop by Specification Table
You can find items with similar specifications from the table below.
Inverter Drives
259 Items
inverter-drives-img
Local Signalling
3 LEDs for local diagnostic 3 LEDs (dual colour) for embedded communication status 4 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage, 1 LED (red) for DC bus energized, 3 LEDs (dual colour) for embedded communication status 4 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage 3 LEDs for local diagnostic, 2 LEDs for local diagnostic 1 LED (yellow) for embedded communication status 2 LEDs (dual colour) for communication module status 1 LED (red) for presence of voltage, Local diagnostic: 3 LED (mono/dual colour) Embedded communication status: 5 LED (dual colour) Communication module status: 2 LED (dual colour) Presence of voltage: 1 LED (red)
Range of Product
Altivar 212, Easy Altivar 610, Altivar 12, Altivar Machine ATV320, Altivar Process ATV600
Mounting Mode
Cabinet mount, Wall Mount, DIN Rail, Cabinet Mount, Panel Mount
Standard
CE, CSA, CE, UL, CE, CSA, UL, ATEX, CE, CSA, cUL, EAC, EN 954-1, EN ISO 13849-1, EN ISO 13849-2, IEC 60204-1, IEC 6100, IEC 61158, IEC 61508, IEC 61784, IEC/EN 60721, TUV, UL 508C, EN/IEC 61800-3 Environment 1 Category C2, EN/IEC 61800-3 Environment 2 Category C3, EN/IEC 61800-5-1, EN/IEC 61800-6, IEC 60721-3, IEC 61000-3-12, IEC 61508, UL508C
IP Degree of Protection
IP20, IP21, IP41, IP00, IP20, IP65, IP54, IP55
Ambient Air Temperature for Operation
-10…50 °C without derating 50…60 °C with current derating 2.2 % per °C, -10…50 °C without derating 50…60 °C with derating factor, 40…50 °C (with derating factor) -15…40 °C (without derating), -15…50 °C (without derating) 50…60 °C (with derating factor), -10…40 °C (without derating) 40…60 °C (with derating factor)
Operating Altitude
<= 3000 m with current derating above 1000m, 1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m <= 1000 m without derating, <= 1000 m without derating 1000...4800 m with current derating 1 % per 100 m, <= 1000 m without derating 1000...3000 m with current derating 1 % per 100 m, > 1000...2000 m with current derating 1 % per 100 m <= 1000 m without derating
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
Inverter Drives dari SCHNEIDER ELECTRIC
Temukan dan bandingkan barang serupa
Lebih Dari Inverter Drives
Perluas pencarian anda dengan pilihan yang lebih bervariasi
Baru Saja Dilihat Produk
Bandingkan dan Rujuk ke item yang dilihat sebelumnya
Image
Atas