This XPSAC safety module monitors emergency shutdown pushbuttons and limit switches. It meets the requirements of Performance Level PL e/Category 4 conforming to standard EN/ISO 13849-1 and SILCL3 conforming to EN/IEC 61508 and EN/IEC 62061. It can be used for monitoring emergency stop circuits conforming to standards EN/ISO 13850 and EN/IEC 60204-1. 24V AC/DC supply allows direct supply via an auxiliary transformer, like ABT7 or ABL6, allowing saving at installation time. It has removable terminals for easier and better control wires tightening, thus improving installation reliability. It has additional solid-state output for communication with PLCs about safety status of your process.
- Range of Product: Preventa Safety Automation
- Product or Component Type: Preventa Safety Module
- Safety Module Name: XPSAC
- Safety Module Application: For emergency stop and switch monitoring
- Function of Module:
- Switch monitoring
- Emergency stop
- Safety Level:
- Can reach PL e/Category 4 conforming to EN/ISO 13849-1
- Can reach SILCL 3 conforming to EN/IEC 62061
- Safety Reliability Data:
- MTTFd = 210.4 years conforming to EN/ISO 13849-1
- DC > 99% conforming to EN/ISO 13849-1
- PFHd = 3.56E-9 1/h conforming to EN/IEC 62061
- Type of Start: Unmonitored
- Connections - Terminals:
- Captive screw clamp terminals, removable terminal block, various configurations, with double bezel
- Output Type: Relay instantaneous opening, 3 NO circuit(s), volt-free
- Number of Additional Circuits: 1 solid-state output
- Rated Supply Voltage ([Us]):
- 24 V AC - 20...10 %
- 24 V DC - 20...20 %
- Complementary:
- Supply Frequency: 50/60 Hz
- Maximum Power Consumption:
- [Uc] Control Circuit Voltage: 24 V
- Breaking Capacity:
- 180 VA holding AC-15 C300 relay output
- 1800 VA inrush AC-15 C300 relay output
- Output Thermal Current: 6 A per relay for relay output
- [Ith] Conventional Free Air Thermal Current: 10.5 A
- Associated Fuse Rating:
- 4 A gG or gL for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
- 6 A fast blow for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
- Minimum Output Current: 10 mA for relay output
- Minimum Output Voltage: 16 V for relay output
- Maximum Response Time on Input Open: 100 ms
- [Ui] Rated Insulation Voltage: 300 V (pollution degree 2) conforming to IEC 60947-5-1 and DIN VDE 0110 part 1
- [Uimp] Rated Impulse Withstand Voltage: 4 kV overvoltage category III conforming to IEC 60947-5-1 and DIN VDE 0110 part 1
- Local Signalling: 2 LEDs
- Current Consumption:
- 40 mA at 24 V DC on power supply
- 90 mA at 24 V AC on power supply
- Mounting Support: 35 mm symmetrical DIN rail
- Net Weight: 0.16 kg
- Environment:
- Standards:
- EN/ISO 13850
- EN/IEC 60947-5-1
- EN 60204-1
- EN 1088/ISO 14119
- Product Certifications: UL, CSA, TÜV
- IP Degree of Protection:
- IP20 (terminals) conforming to EN/IEC 60529
- IP40 (enclosure) conforming to EN/IEC 60529
- Ambient Air Temperature for Operation: -10…55 °C
- Ambient Air Temperature for Storage: -25…85 °C