Abb S202M-C63 Mcb 2P 63A Curve C 10KA

  • System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.
  • oduct Net Width:35 mm
  • Product Net Height:88 mm
  • Product Net Depth / Length:69 mm
  • Product Net Weight:0.25 kg
  • Unit of measurement : Pcs

Technical

  • Standards:IEC/EN 60898-1
  • CSA 22.2 No. 235
  • IEC/EN 60947-2
  • UL 1077
  • Tripping Characteristic:C
  • Rated Operational Voltage:acc. to IEC 60898-1 400 V AC
  • acc. to IEC 60947-2 440 V AC
  • Operational Voltage:Maximum (Incl. Tolerance) 125 V DC
  • Maximum (Incl. Tolerance) 440 V AC
  • Minimum 12 V AC
  • Minimum 12 V DC
  • Rated Insulation Voltage (Ui):acc. to IEC/EN 60664-1 440 V
  • Rated Impulse Withstand Voltage (Uimp):4 kV
  • at 2000 m 5 kV
  • at Sea Level 6.2 kV
  • Dielectric Test Voltage:50/60 Hz, 1 min: 2 kV
  • Input Voltage Type:AC/DC
  • Rated Current (In):63 A
  • Rated Short-Circuit Capacity:(AC) 10 kA
  • (230 V AC) 10 kA
  • (400 V AC) 10 kA
  • Rated Ultimate Short-Circuit Breaking Capacity (Icu):(230 V AC) 25 kA
  • (400 V AC) 15 kA
  • (440 V AC) 15 kA
  • Rated Conditional Short-Circuit Current (Inc):(230 V) 10 kA
  • (400 V) 20 kA
  • Rated Service Short-Circuit Breaking Capacity (Ics):(133 V AC) 15 kA
  • (230 V AC) 7.5 kA
  • Frequency (f):50 Hz
  • Rated Frequency (f):50 / 60 Hz
  • Power Loss:9.6 W
  • at Rated Operating Conditions per Pole 4.8 W
  • Power Supply Connection:Arbitrary
  • Contact Position Indication:Red ON / Green OFF
  • Energy Limiting Class:3
  • Electrical Endurance:10000 AC cycle
  • Mechanical Endurance:20000 cycle
  • Number of Poles:2
  • Number of Protected Poles:2
  • Overvoltage Category:III
  • Tightening Torque:2.8 N·m
  • Screw Terminal Type:Failsafe Bi-directional Cylinder-lift Terminal
  • Actuator Marking:I / O
  • Actuator Material:Insulation Group II, Black, Sealable
  • Housing Material:Insulation Group II, RAL 7035
  • Mounting on DIN Rail:TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
  • TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
  • Mounting Position:any
  • Recommended Screw Driver:Pozidriv 2
  • Accessories Available:Yes
  • Connecting Capacity:Busbar 10 / 10 mm²
  • Flexible with Ferrule 0.75 ... 25 mm²
  • Flexible 0.75 ... 25 mm²
  • Rigid 0.75 ... 35 mm²
  • Stranded 0.75 ... 35 mm²
  • Installation Size:acc. to DIN 43880 1
  • Terminal Type:Screw Terminals