Current
Voltage
Frequency
Power factor
Energy
Active and reactive power
Display Type
Monochrome graphic LCD
Standards
UL 61010-1
EN 50470-3
EN 50470-1
IEC 62053-22:2020
IEC 60529
IEC 62053-24
IEC 61557-12:2015
IEC 62053-23:2020
IEC 62052-11:2020
IEC 62052-31:2015
Ambient Air Temperature for Operation
-25…70 °C meter
-20…70 °C display
-25…-20 °C (with reduced performance) display
Width
96 mm
This spec is not available in the specification table.
Device Short Name
PM5110
This spec is not available in the specification table.
Product or Component Type
Power meter
This spec is not available in the specification table.
Product Name
PowerLogic PM5000
This spec is not available in the specification table.
Depth
72 mm
This spec is not available in the specification table.
Device Application
Power monitoring
This spec is not available in the specification table.
Mounting Support
Framework
This spec is not available in the specification table.
Height
96 mm
This spec is not available in the specification table.
Mounting Mode
Flush-mounted
This spec is not available in the specification table.
Accuracy class
Class 0.5S active energy conforming to IEC 62053-22
This spec is not available in the specification table.
Network Frequency
50 Hz
60 Hz
This spec is not available in the specification table.
Sampling rate
64 samples/cycle
This spec is not available in the specification table.
Measurement current
50…8500 mA
This spec is not available in the specification table.
Communication Port Protocol
Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V
JBUS
This spec is not available in the specification table.
Communication port support
RS485
This spec is not available in the specification table.
Number of outputs
1 digital
This spec is not available in the specification table.
Connections - Terminals
Voltage circuit: screw terminal block4
Control circuit: screw terminal block2
Current transformer: screw terminal block6
Input/output circuit: screw terminal block6
RS485 link: screw terminal block4
This spec is not available in the specification table.
Product certifications
CE conforming to IEC 61010-1
CULus conforming to UL 61010-1
This spec is not available in the specification table.
IP Degree of Protection
IP54 display: conforming to IEC 60529
IP30 rear: conforming to IEC 60529
This spec is not available in the specification table.
Pollution Degree
2
This spec is not available in the specification table.
Relative Humidity
5…95 % at 50 °C non-condensing
This spec is not available in the specification table.
Ambient Air Temperature for Storage
-40…85 °C
This spec is not available in the specification table.
Operating Altitude
2000 m CAT III
This spec is not available in the specification table.
Power quality analysis
up to the 15th harmonic
This spec is not available in the specification table.
supply voltage
90...450 V AC 45...65 Hz
100...300 V DC
This spec is not available in the specification table.
type of network
1P + N
3P + N
3P
This spec is not available in the specification table.
Maximum power consumption in VA
11 VA at 415 V
This spec is not available in the specification table.
Ride-through time
80 ms 120 V AC typical
100 ms 230 V AC typical
100 ms 415 V AC typical
50 ms 125 V DC typical
This spec is not available in the specification table.
Display resolution
128 x 128 pixels
This spec is not available in the specification table.
Analogue input type
Voltage (impedance 5 MOhm)
Current (impedance <= 0.3 mOhm)
This spec is not available in the specification table.
Measurement voltage
35…760 V AC 45...65 Hz between phases
20…440 V AC 45...65 Hz between phase and neutral
This spec is not available in the specification table.
Frequency measurement range
45…65 Hz
This spec is not available in the specification table.
Measurement accuracy
Active energy +/- 0.5 %
Reactive energy +/- 2 %
Active power +/- 0.5 %
Apparent power +/- 0.5 %
Frequency +/- 0.05 %
Power factor +/- 0.5
Current +/- 0.5 %
Voltage +/- 0.5 %
Apparent energy +/- 0.5 %
Reactive power +/- 2 %
This spec is not available in the specification table.
data recording
Time stamping
Min/max of instantaneous values
This spec is not available in the specification table.
Electromagnetic Compatibility
Voltage dips and interruptions immunity test class A conforming to IEC 61000-4-11
Limits for harmonic current emissions class A conforming to IEC 61000-3-2
Electrostatic discharge level 4 conforming to IEC 61000-4-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
Conducted and radiated emissions - test level: 150 kHz...80 MHz class B conforming to EN 55022
Immunity to conducted disturbances - test level: 150 kHz...80 MHz conforming to IEC 61000-4-6
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Surge immunity test class B conforming to IEC 61000-4-5
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
This spec is not available in the specification table.