Shopping List
Shopping List
AUD - AU$
Image
/
/
/
/
Schneider Electric LC1D95R7 Contactor, Tesys Deca, 3P(3NO), AC-3/AC-3e, <=440V, 95A, 440V, Ac 50/60Hz Coil, Screw Clamp Terminals
Schneider Electric LC1D95R7 Contactor, Tesys Deca, 3P(3NO), AC-3/AC-3e, <=440V, 95A, 440V, Ac 50/60Hz Coil, Screw Clamp Terminals
Image
Image
Specifications
infotip-icon
View other Contactors dimensions or variations
Please select at least one specification below.
Device Short Name
LC1D
Range Of Product
TeSys Deca
Depth
130 mm
Pole Contact Composition
3 NO
Poles Description
3P
Contactor Application
Resistive load Motor control
Compatibility Code
LC1D
This spec is not available in the specification table.
Standards
EN/IEC 60947-1 EN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 UL 60947-5-1 CSA C22.2 No 60947-4-1 CSA C22.2 No 60947-5-1 GB/T 14048.4
This spec is not available in the specification table.
[Ui] Rated Insulation Voltage
Power circuit: 1000 V conforming to IEC 60947-4-1 Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified
This spec is not available in the specification table.
[Uimp] Rated Impulse Withstand Voltage
8 kV conforming to IEC 60947
This spec is not available in the specification table.
Mounting Support
Plate Rail
This spec is not available in the specification table.
Connections - Terminals
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end Power circuit: connector 1 4…50 mm² - cable stiffness: flexible without cable end Power circuit: connector 2 4…25 mm² - cable stiffness: flexible without cable end Power circuit: connector 1 4…50 mm² - cable stiffness: flexible with cable end Power circuit: connector 2 4…16 mm² - cable stiffness: flexible with cable end Power circuit: connector 1 4…50 mm² - cable stiffness: solid without cable end Power circuit: connector 2 4…25 mm² - cable stiffness: solid without cable end
This spec is not available in the specification table.
Height
127 mm
This spec is not available in the specification table.
Ip Degree Of Protection
IP20 front face conforming to IEC 60529
This spec is not available in the specification table.
Pollution Degree
3
This spec is not available in the specification table.
Mechanical Durability
4 Mcycles
This spec is not available in the specification table.
Electrical Durability
1.2 Mcycles 95 A AC-3 1.3 Mcycles 125 A AC-1 1.2 Mcycles 95 A AC-3e
This spec is not available in the specification table.
Operating Altitude
0...3000 m
This spec is not available in the specification table.
Tightening Torque
Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2 Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm Power circuit: 12 N.m - on connector hexagonal screw head 4 mm Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
This spec is not available in the specification table.
[Ue] Rated Operational Voltage
Power circuit: <= 690 V AC 25...400 Hz
This spec is not available in the specification table.
[Ie] Rated Operational Current
95 A (at <60 °C) at <= 440 V AC-3 for power circuit 125 A (at <60 °C) at <= 690 V AC-1 for power circuit 95 A (at <60 °C) at <= 440 V AC-3e for power circuit
This spec is not available in the specification table.
[Uc] Control Circuit Voltage
440 V AC 50/60 Hz
This spec is not available in the specification table.
Inrush power in VA
245 VA 60 Hz cos phi 0.75 (at 20 °C)<br />245 VA 50 Hz cos phi 0.75 (at 20 °C)
This spec is not available in the specification table.
Hold-in power consumption in VA
26 VA 60 Hz cos phi 0.3 (at 20 °C)<br />26 VA 50 Hz cos phi 0.3 (at 20 °C)
This spec is not available in the specification table.
Heat dissipation
6…10 W at 50/60 Hz
This spec is not available in the specification table.
Range
TeSys
This spec is not available in the specification table.
Utilisation Category
AC-3 AC-3e AC-4 AC-1
This spec is not available in the specification table.
Motor Power Kw
25 kW at 220...230 V AC 50 Hz (AC-3) 45 kW at 380...400 V AC 50 Hz (AC-3) 45 kW at 415...440 V AC 50 Hz (AC-3) 55 kW at 500 V AC 50 Hz (AC-3) 45 kW at 660...690 V AC 50 Hz (AC-3) 15 kW at 400 V AC 50 Hz (AC-4) 25 kW at 220...230 V AC 50 Hz (AC-3e) 45 kW at 380...400 V AC 50 Hz (AC-3e) 45 kW at 415...440 V AC 50 Hz (AC-3e) 55 kW at 500 V AC 50 Hz (AC-3e) 45 kW at 660...690 V AC 50 Hz (AC-3e)
This spec is not available in the specification table.
Protective Cover
With
This spec is not available in the specification table.
Motor Power Hp
7.5 hp at 120 V AC 60 Hz for 1 phase motors 15 hp at 230/240 V AC 60 Hz for 1 phase motors 30 hp at 200/208 V AC 60 Hz for 3 phases motors 30 hp at 230/240 V AC 60 Hz for 3 phases motors 60 hp at 460/480 V AC 60 Hz for 3 phases motors 60 hp at 575/600 V AC 60 Hz for 3 phases motors
This spec is not available in the specification table.
[Ith] Conventional Free Air Thermal Current
10 A (at 60 °C) for signalling circuit 125 A (at 60 °C) for power circuit
This spec is not available in the specification table.
Irms Rated Making Capacity
1100 A at 440 V AC for power circuit conforming to IEC 60947 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1
This spec is not available in the specification table.
Rated Breaking Capacity
1100 A at 440 V for power circuit conforming to IEC 60947
This spec is not available in the specification table.
[Icw] Rated Short-Time Withstand Current
1100 A 40 °C - 1 s for power circuit 800 A 40 °C - 10 s for power circuit 400 A 40 °C - 1 min for power circuit 135 A 40 °C - 10 min for power circuit 140 A - 100 ms for signalling circuit 120 A - 500 ms for signalling circuit 100 A - 1 s for signalling circuit
This spec is not available in the specification table.
Associated Fuse Rating
10 A gG for signalling circuit conforming to IEC 60947-5-1 200 A gG at <= 690 V coordination type 1 for power circuit 160 A gG at <= 690 V coordination type 2 for power circuit
This spec is not available in the specification table.
Average Impedance
0.8 mOhm - Ith 125 A 50 Hz for power circuit
This spec is not available in the specification table.
Power Dissipation Per Pole
12.5 W AC-1 7.2 W AC-3 7.2 W AC-3e
This spec is not available in the specification table.
Safety Reliability Level
B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1
This spec is not available in the specification table.
Control Circuit Type
AC at 50/60 Hz
This spec is not available in the specification table.
Coil Technology
Without built-in suppressor module
This spec is not available in the specification table.
Control Circuit Voltage Limits
0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz 0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz 1...1.1 Uc (55…70 °C):operational AC 50/60 Hz
This spec is not available in the specification table.
Operating Time
20...35 ms closing 6...20 ms opening
This spec is not available in the specification table.
Auxiliary Contact Composition
3600 cyc/h 60 °C
This spec is not available in the specification table.
Maximum Operating Rate
1 NO + 1 NC
This spec is not available in the specification table.
Signalling Circuit Frequency
25...400 Hz
This spec is not available in the specification table.
Auxiliary Contacts Type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 type mirror contact 1 NC conforming to IEC 60947-4-1
This spec is not available in the specification table.
Minimum Switching Voltage
17 V for signalling circuit
This spec is not available in the specification table.
Minimum Switching Current
5 mA for signalling circuit
This spec is not available in the specification table.
Insulation Resistance
> 10 MOhm for signalling circuit
This spec is not available in the specification table.
Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
This spec is not available in the specification table.
Protective Treatment
TH conforming to IEC 60068-2-30
This spec is not available in the specification table.
Climatic Withstand
conforming to IACS E10 exposure to damp heat
This spec is not available in the specification table.
Permissible Ambient Air Temperature Around The Device
-40…60 °C 60…70 °C with derating
This spec is not available in the specification table.
Fire Resistance
850 °C conforming to IEC 60695-2-1
This spec is not available in the specification table.
Flame Retardance
V1 conforming to UL 94
This spec is not available in the specification table.
Mechanical Robustness
Vibrations contactor open (2 Gn, 5...300 Hz) Shocks contactor open (8 Gn for 11 ms) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor closed (10 Gn for 11 ms)
This spec is not available in the specification table.
Product Description
Highly Matched Items
View items that have the same or are a close match to the specifications of this item
Contactors from SCHNEIDER ELECTRIC
Source & compare similar products
More from Contactors
Expand your search with a wider selection
Recently Viewed Products
Compare & Refer to previously viewed items
Image
Top