Shopping List
Shopping List
AUD - AU$
Image
/
/
/
/
Abb PSR37-600-70 Soft Starter 600V 22KW
Abb PSR37-600-70 Soft Starter 600V 22KW
Brand:
ABB
Model:
PSR37-600-70
Image
Image
Product Description

Abb PSR37-600-70 Soft Starter 600V 22KW


  • The softstarter PSR37-600-70 has a rated maximum operational current of 37 A with an operating voltage span from 208...600 V AC. The rated control voltage is between 100...240 V AC at 50/60 Hz. PSR features a two-phase control soft start and stop through a voltage ramp. It has built-in bypass for easy installation and energy saving. A RUN and a TOR signal is available from a relay output in NO (normally open state). The start/stop ramp and time is easy to set by three potentiometers on the front. PSR is often used in combination with a manual motor starter (MMS) from ABB, so mechanical connection kits are available. Another popular option is Fieldbus communication, which can be enabled by an external adaptor and a Fieldbus plug. The PSR range is our most compact softstarters with basic functionality and values. They are suitable for small three-phase motors with nominal currents from 3...105 A and can manage up to 100 starts per hour. Common applications are, for example, pumps, fans, compressors, and conveyors.
  • Product Net Width:153 mm
  • Product Net Height:187 mm
  • Product Net Depth / Length:54 mm
  • Product Net Weight:1 kg
  • Unit of measurement : Pcs

Technical

  • Rated Operational Voltage:208 ... 600 V AC
  • Rated Control Supply Voltage (Us):100 ... 240 V AC
  • Rated Control Circuit Voltage (Uc):24 V DC
  • Rated Frequency (f):50/60 Hz
  • Main Circuit 50 / 60 Hz
  • Rated Operational Power - In-Line Connection (Pe):(230 V) 7.5 kW
  • (400 V) 18.5 kW
  • (500 V) 22 kW
  • Rated Operational Current - In-Line Connection (Ie):37 A
  • Service Factor Percentage:100 %
  • Overload Protection:Recommended MS450 28 ... 40
  • Integrated Electronic Overload:No
  • Adjustable Rated Motor Current Ie:No
  • Starting Capacity at Maximum Rated Current Ie:4xIe for 6s
  • Ramp Time:0 ... 20 second [unit of time]
  • 1 ... 10 second [unit of time]
  • Initial Voltage During Start:40 ... 70 %
  • Step Down Voltage Special Ramp:100 ... 60 %
  • Current Limit Function:No
  • Switch for Inside Delta Connection:No
  • Run Signal Relay:Yes
  • By-pass Signal Relay:Yes
  • Fault Signal Relay:No
  • Overload Signal Relay:No
  • Signal Indication Completed Start Ramp (LED):Green
  • Signal Indication Ready to Start/Standby ON (LED):Green
  • Signal Indication Running R (LED):Green
  • Signal Indication Ramping Up/Down (LED):Green
  • Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time:10
  • Communication:FiledBusPlug(Optional)
  • Degree of Protection:IP10
  • Terminal Type:Screw Terminals
  • Connecting Capacity Main Circuit:Rigid 1x 6 ... 35 mm²
  • Rigid 2 x 6 ... 16 mm²
  • Connecting Capacity Control Circuit:1 x 0.75 ... 2.5
  • 2 x 0.75 ... 2.5 mm²
  • Rigid 1 x 0.75 ... 2.5 mm²
  • Rigid 2 x 0.75 ... 1.5 mm²
  • Connecting Capacity Supply Circuit:Rigid 1 x 0.75 ... 2.5 mm²
  • Tightening Torque:Control Circuit 0.6 N·m
  • Main Circuit 4 N·m
  • Supply Circuit 0.6 N·m
  • Product Main Type:PSR37
  • Function:Soft start with voltage ramp
  • Soft stop with voltage ramp
AU $ 1,428.97
UnitsDiscountUnit Price
1-AU $ 1,428.97
Quantity:
EA
Stock:
2 EA in stock
location
In Seller's Warehouse
Image
Lead time of 60 working days required.
Item will be ready to dispatch within the lead time specified.
Shop by Specification Table
You can find items with similar specifications from the table below.
Motor Starter
197 Items
motor-starter-img
Rated Current
62 A, 250 A, 480 A, 790 A, 320 A
Rated Voltage
440 V, 415 V, 208 → 690 V ac, 240 V, 480 V
Standards and Certifications
CCC, CE, CSA, EAC, UL, CE, CSA, CSA C22.2 No 14, C-Tick, EAC, EN 61131-2, EN/IEC 60068-2-27, EN/IEC 60068-2-30, EN/IEC 60068-2-6, EN/IEC 61000-4-4, EN/IEC 61000-4-5, EN/IEC 61000-4-6, IEC 60068-2-27, IEC 61131-2, NOM, UL, UL 508, CSA, UL, CCC, CE, CSA, UL, ABS, ATEX, BV, CCC, CSA, CSA C22.2 No. 14, C-TICK, DNV, EAC, EN 60947-4-1, EN/IEC 60068, EN/IEC 60068-2-30, EN/IEC 60070-2-11, EN/IEC 60695-2-12, EN/IEC 60947-1, EN/IEC 60947-4-1, EN/IEC 61000-4-5, GL, IACS E10, IEC 60947-4-1, KERI, LROS (Lloyds register of shipping), NOM, RINA, RMRoS, UL, UL 508, UL 94
Coil Voltage
110...240 V AC 110...220 V DC, 24 V AC, 380 V AC 50/60 Hz, 415 V AC 50/60 Hz, 220 V AC 50/60 Hz
Width
55 mm, 30 mm, 45 mm, 22.5 mm, 265 mm
Depth
115 mm, 114.5 mm, 170 mm, 209 mm, 139 mm
[Uimp] Rated Impulse Withstand Voltage
4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1, 4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV communication circuit conforming to EN/IEC 60947-4-1, 6 kV conforming to IEC 60947-6-2, 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV communication circuit conforming to EN/IEC 60947-4-1 0.8 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1, 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 0.8 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1
Motor Starter from ABB