- Extended Product Type: OT16F3
- Product ID: 1SCA104811R1001
- EAN: 6417019389554
- Catalog Description: OT16F3 Switch-Disconnector
- Long Description: 3-pole, front operated, base mounted, DIN-rail mountable switch-disconnector / non-fusible disconnect switch with protected clamp terminals
- Handle and Shaft: Not included
Technical Specifications
- Cable Cross-Section: Cu 0.75–10 mm²
- Color: Grey
- Conventional Free-Air Thermal Current (Ith): 25 A at 40°C
- Conventional Thermal Current (Ithe): 25 A, fully enclosed
- Distance Between Phases: Standard
- Handle Type: Knob
- Mechanical Durability: 20,000 operations
- Mounting Type: Base mounting
- Number of Poles: 3P
- Operating Mode: Front
- Position of Line Terminals: Top In – Bottom Out / Bottom In – Top Out
- Power Loss: 0.3 W per pole at rated operating conditions
- Terminal Type: Screw terminals
- Tightening Torque: 0.8 N·m according to IEC 60947-1
- Wire Stripping Length: 9–10 mm for main circuit
- Recommended Screwdriver: Pozidriv 2 for main circuit
- Special Functions: None
- Switch Operating Mechanism: Mechanism on top of the switch
- Standards: IEC 60947-3 / UL 508 / CSA C22.2 No. 14
Connecting Capacity – Main Circuit
- Flexible with Ferrule: 1 × Cu 0.75–4 mm²
- Solid: 1 × Cu 0.75–6 mm²
- Flexible: 1 × Cu 0.75–10 mm²
- Stranded: 1 × Cu 0.75–10 mm²
Rated Electrical Characteristics
- Rated Insulation Voltage (Ui): 750 V according to IEC/EN 60664-1
- Rated Impulse Withstand Voltage (Uimp): 8 kV
- Rated Operational Voltage: 750 V, main circuit
- Rated Operational Current AC-21A (Ie):
- 16 A at 380–415 V
- 16 A at 500 V
- 16 A at 690 V
- Rated Operational Current AC-22A (Ie):
- 16 A at 380–415 V
- 16 A at 500 V
- 16 A at 690 V
- Rated Operational Current AC-23A (Ie):
- 16 A at 380–415 V
- 16 A at 500 V
- 10 A at 690 V
- Rated Operational Power AC-23A (Pe):
- 3 kW at 220–240 V
- 7.5 kW at 400–415 V
- 7.5 kW at 500 V
- 7.5 kW at 690 V
- Rated Conditional Short-Circuit Current (Inc):
- 50 kA with 40 A fuse at ≤415 V
- 50 kA with 25 A fuse at 690 V
- Rated Short-Circuit Making Capacity (Icm): 0.71 kA at 690 V
- Rated Short-Time Withstand Current (Icw): 0.5 kA for 1 second
UL/CSA Specifications
- Maximum Operating Voltage: 600 V
- Ampere Rating: 20 A
- Tightening Torque: 7 in-lb
- Horsepower Rating:
- 1 Hp at 110–120 V AC, single phase
- 2 Hp at 240 V AC, single phase
- 5 Hp at 440–480 V AC, single phase
- 7.5 Hp at 550–600 V AC, single phase
- 5 Hp at 220–240 V AC, three phase
- 10 Hp at 440–480 V AC, three phase
- 10 Hp at 550–600 V AC, three phase